Offgrid water pumping station in Colombia

Offgrid system for a water pumping station in Colombia

The water distribution system of the Colombian town of Rubiales in the Meta department was previously using a diesel generator for its pumping station. As both fuel and maintenance of a diesel generator are expensive, they were looking for a renewable energy system to replace it completely. In Colombia hydropower accounts for about two-thirds of the generation capacity (2016).

 

A solar system to supply water to an entire village

This is a complete offgrid system for a pumping station with two submerged pumps. One pump draws water from an 80m deep well into an 80m3 water storage tank.  The second pump is transferring water from that tank to a 50m3 storage tank in a water tower located 60 m above ground.  The water then flows by gravity to the town users, about 100 homes.

The solar system is composed of a 54kWp solar field, four 48V battery banks each of 2405Ah C-100, nine solar charge controllers in parallel, and three inverter/chargers in a 3-phase system configuration.

variostring installation
rcc picture

How about the project?

The habitants of the Rubiales town are now solely using solar power for their local aqueduct. As additional benefits, its operation is silent, and there is no pollution.

Replacing the existing diesel generator with an off-grid system to power the pumping station was not only a technical challenge, but it also meant a reorganisation of the pumping stations running times in order to make the system efficient. The pumps are still running 9 hours per day; however, they start a few hours later in order to fully benefit from the power generation close to midday when the sun is at its peak. In the beginning, this change was difficult for the people as they were used to having the water supply already at five o’clock in the morning.


Currently, some users do not have water tanks, meters, or valves to close the pipes, and the clear water waste is big, approximately 30% of the water supply. If they would put in valves to close the pipes and save the water, the need for pumping hours would decrease, the availability of water would be extended and they could supply water to new users.

Date:

October 21, 2022

Components:
Studer contact:
The customer:
Date:

October 21, 2022

Components:
Studer contact:
The customer:
Details
DateOctober 21, 2022Product54 kWp of solar modules | 96x 9620 Ah batteries | 3x xtender inverter/charger xth 8000-48 115Vac 60Hz | 9x variostring vs 120 charge controllersStuder contactDaniel MedinaShare
Studer Innotec
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.